Control unit KEA 211-NP 2-1
replaces SEG NP 2-1
Technical Data
Hardware
Operating panel
- Display for indication of fault signals, counter readings, analogue values and status signals
- 4 LED indicators for the display of additional operation indicators
- USB interface for parameterization
Measurement
- 3-phase (to N phases) mains voltage monitor for nominal voltage 231/400 Volt, adjustable in 1 Volt steps.
- Adjustable switching points: 50 - 300 Volt.
- Mains frequency 45 to 65 Hz, adjustable in 0.01 Hz steps of 40 to 70 Hz.
- 2-phase generator voltage monitor for nominal voltage 400 V, adjustable in 1 Volt steps. Adjustable 250 - 480 Volt.
- Generator frequency 45 to 65 Hz, adjustable in 0.01 Hz steps of 40 to 70 Hz.
- Battery voltage monitor.
Digital inputs and outputs
- Input for generator D+ with pre-excitation for AC generators.
- 10 connections for alarm contacts.
- 18 general control inputs.
- 17 output relays, of which 14 are parametrisable, starting and stop relay contact load max. 16 Amp., 3 relays 35 DC, max. 1 Amp., 10 relays max. 10 Amp.
- Input for pick-up for the speed measurement.
Serial interface
- USB interface for parametrisation, for coupling via an additional mode to a control system or to a remote monitoring.
Technical Data
Design
- Device for panel mounting, Dimensions (WxHxD): 260 x 170 x 100 mm,
- Weight: approx. 2,2 kg, any installation position, Protection type (built-in) IP 44
- one-to-one interchangeable
General
- Ambient temperature:
- Storage-20°C ... +70°C,
- Operation 0°C ... +55°C,
- Supply voltage switchable
- 9-12-15V or
- 14-24-35V DC,
- Standards/regulations: DIN VDE 0160
Order Number
Product Name: KEA 211-NP 2-1
Article-Number: 2A211NP000
Downloads
Product overview
Documentation
Software